C120H C10 1P schneider miniature circuit breakers in stock

C120H C10 1P

1/pieces

Shenzhen

T/T, paypal, Western Union

PDF Down

# Attribute Parameter
1OriginGermany
2Tripping curvesB,C,D
3breaking capacity15Ka-45Ka
4Current10-125A
5WarrantyOne year

Schneider miniature circuit breakers

C120H circuit-breakers

15kA, B, C curves - AS/NZS 4898

15kA, D curve AS 3947-2

circuit-breakers up to125 A


functions

The circuit-breakers combine the following functions:

● protection of circuits against short-circuit currents,

● protection of circuits against overload currents,

● control,

● isolation

● protection of persons against indirect contact.

      

Description

technical data common to C120H circuit breakers

● power circuit

○ power circuit v current rating: 10 to125 A

○ voltage rating 415 V AC

○ insulation voltage Ui: 500 V

○ impulse withstand voltage Uimp: 6 kV

○ breaking capacity:

○ mechanical durability:

- 20000 cycles (O-C)

○ electrical durability:

-63 A: 10000 cycles (O-C)

- 80…125 A: 5000 cycles (O-C)

○ I2t classification: 3

○ isolation with positive contact indication: opening is indicated by a green strip on the device operating handle. This indicator shows opening of all the poles

○ foolproof terminal design

- moving barrier prevents incorrect cable insertion

- cable strand centering guides ensure correct cable positions and strand grouping

○ bistable din clip: simplifies disassembly

○ 63 to125A:

- up to35mm2 flexible with cable end

- up to50mm2  stranded

 

 

B curve

utilisation

when there are small inrush currents

(generators, long cables).

technical data

● power circuit

○ tripping curve:

the magnetic trip units operate between 3 and5 In.

 

C curve

utilisation

cables feeding conventional loads.

technical data

● power circuit

○ tripping curves: the magnetic trip unit operates between 5 and10 In

 

D curve

utilisation

loads with a high inrush current

(motors, transformers).

technical data

● power circuit

○ tripping curve:

the magnetic trip units operate between 10 and14 In.

 

B,C breaking capacity

- according to AS/NZS 4898 Icu ultimate breaking capacity (0-C0 cycle):

Rating

(A)

Type

Voltage

(V)

Breaking capacity

Icu (A)

10...125

1P,2P,3P,4P

240/415

15000

D breaking capacity

according to AS3947-2 Icu ultimate breaking capacity (O-CO cycle)

Rating

(A)

Type

Voltage

(V)

Breaking capacity

Icu (A)

10...125

1P

240

15000

1P

415

45000

2P,3P,4P

400-415

150

 